XM31-915-HP - 10018235
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-915-HP
Firmware V2.06.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 126.20 V
Current 3.14 A
Power 368 W
Frequency 60 Hz
Tap Status Buck tap
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 4,637 Wh
Output
Voltage 87.05 V
Power 254 W
Apparent Power 292.48 VA
Frequency 60.01 Hz
Percent Load 22.40 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 3.36 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Enable
Total Standby Events 43
Time Since Last Standby Event 0d 0h:00m
Time in Last Standby Event 0d 0h:00m
Total Time in Standby 239 min
Standby Events Since Reset 21
Time in Standby Since Reset 0 min
Time Since Reset 240 day(s)
Total Run Time 240 day(s)
Transformer Run Time 240 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 9.6 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 7 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2023 EnerSys. All Rights Reserved.